Accurate Quotation ×
Electrical Engineering > Low Voltage Distribution Equipment > Power Transformer > Xuxiang > S11 Series 50~31500kVA/35kV Double-Wi...
S11 Series 50~31500kVA/35kV Double-Winding Non-excitation Voltage Regulation Power Transformer

  • S11 Series 50~31500kVA/35kV Double-Winding Non-excitation Voltage Regulation Power Transformer

Share:
S11 Series 50~31500kVA/35kV Double-Winding Non-excitation Voltage Regulation Power Transformer
1 Reference Price:Get Latest Price
Chat Now 1 / EA (Min. Order)
Warranty: One Year
After-sales Service: Engineers available to service machinery overseas
Shipping:
Support Sea freight · Land freight · Air freight
Payment Method:
S11 Series 50~31500kVA/35kV Double-Winding Non-excitation Voltage Regulation Power Transformer
S11 Series 50~31500kVA/35kV Double-Winding Non-excitation Voltage Regulation Power Transformer
Quantity:
- + /EA
Please leave your contact information and the products you want to visit. Our engineers will take you to visit 12 subsidiaries of XCMG Group and their related products online.

Name:

Country:

Please fill in the country correctly, we will present in different languages.

*Email:

Mobile phone:

Other:

  • Summary
  • Details
Summary
Details
  • Product Name:G60065389DF4A7
  • Display online time:2021-01-19
  • weight:111.000kg
  • Warranty Period:3 Months
  • After-sales Service Provided:Engineers available to service machinery overseas
  • Warranty:3 Months
  • Certification:CE/ISO9001
  • Condition:NEW

Product Features

1. The low voltage winding uses copper flat wire or copper foil winding structure, while the high voltage winding often adopts multi-layer cylinder or continuous structure, so that the ampere turns of winding is balanced, leakage flux is small, mechanical strength is high and ability to withstand short circuit is strong.

 

2. The core and windings take fastening measures. The transformer body, HV and LV leads and other fastening parts are provided with self-locking locknuts  and unsuspended structure.

 

3. The coil and iron core adopt vacuum drying. The vacuum oil filtering and filling process is used to minimize the moisture inside the transformer.

 

4. The oil tank has novel structure, compact design, and small occupied area.

 

Technical Parameters

Rated
 capacity
(kVA)
Voltage combination Connection
 symbol
No
 -load
 loss
(kW)
Load
 loss
 (kW)
No
 -load
 current
(%)
Impedence
 voltage
(%)
Weight
HV(kV) tapping range
   (%)
LV(kV) Body
Weight
Oil
Weight
Cross
Weight
50 35,38.5 ±5,±2×2.5 0.4 Dyn11,Yyn0 0.19 1.15 2 6.5 290 285 710
100 0.26 1.92 1.8 420 380 1100
125 0.31 2.26 1.7 520 430 1380
160 0.32 2.69 1.6 620 450 1460
200 0.39 3.16 1.5 750 571 1700
250 0.46 3.76 1.4 780 585 1800
315 0.55 4.53 1.4 1030 640 2280
400 0.66 5.47 1.3 1100 660 2400
500 0.77 6.58 1.2 1240 840 2680
630 0.94 7.87 1.1 1300 960 2800
800 1.11 9.41 1 1820 880 3620
1000 1.3 11.54 1 2150 1020 4350
1250 1.58 13.94 0.9 2480 1120 4650
1600 1.91 16.67 0.8 1860 1300 5800
2000 3.15,6.3,10.5 Yd11 2.45 18.38 0.7 2630 1270 5300
2500 2.88 19.67 0.6 3200 1400 6170
3150 3.42 23.09 0.56 7 3780 1600 7100
4000 4.07 27.36 0.56 4480 1840 8630
5000 4.86 31.38 0.48 5400 2090 9950
6300 5.9 35.06 0.48 7.5 6490 2380 11580